AC and DC electro-supplying sources for GSM equipments – indoor use
The cabinet should be used to supply with electric energy the telecommunication equipment including also the mobile phone system. The supplied energy should be with “+” earthed and the voltage system should be of “-48DC” type (on beneficiary request other voltage variants are available)
Description
- The cabinet generally consists of a rectifier and batteries that all together form the continuous source of DC current for the telecommunication equipment
- The rectifiers are designed to transform the alternating current (sinusoidal) from the supplying source in DC and to supply the telecommunication equipment, and in parallel to supply the batteries
- The batteries are designed to store energy and to transmit it to the telecommunication equipment when the supplying source does not function in AC current
- The equipment also contains Control and Monitor Unit (MCU), LVBD type contactor, LVLD type contactor, Temperature Sensor, DC Distribution, Battery Breakers and Three-pole Breaker + Class C Discharger for AC supplying
- The cabinet allows mounting of a maximum 12 rectifiers of 2000W and batteries of maximum 600Ah/48V with front connections
- The system allows large input voltage variations and at a soft-start type starting generates sinusoidal currents. The system can be supplied in AC both with single-phase voltage and three-phase voltage
- The maximum operating temperature for the cabinet is of +60°C; for higher temperatures, each rectifier regulates itself the transmitted power in order not to damage itself
Operating conditions
- Erection location – indoor
- Environment ambient temperature range during operation -40 ÷ +60°C
- Environment ambient temperature range during transportation, storing and erection -40 ÷ +85°C
- Maximum altitude – 4000m
Usage
- UMTS & GSM Base Stations
- Digital Loop Carrier
- 112 (Public safety)
- Telephone Switches
- Data Center
- Internet Hubs
- Optical switches
- GSM Backbone stations
Technical features
System
- Maximum number of rectifiers - 12
- Supplying voltage
- single-phase 230Vac - three-phase 230Vac (D) - three-phase 400Vac+N (Y)
- Frequency – 45, 66 Hz
- Overall dimensions (LxAxH)
- 600x600x1400mm - 600x600x1800mm - 600x600x2200mm
- Approximate weight, without rectifiers and without batteries
- 1400mm/70kg - 1800mm/90kg - 2200mm/110kg
Rectifier
- Rectifier type
- 800W - 1000W - 1800W - 2000W
Control and monitor unit
DC distribution
- priority users – maximum 14 breakers
- non-priority users – maximum 16 breakers
- Battery breaker – maximum 4 x 200A
- Contactors – maximum 4 x 300A (LVBD, LVLD, LVD3)
Applicable standards
- Safety – EN 60950
- EMC
- ETSI EN 300 386 V.1.3.1. (telecom network) - EN 61000-6-3 (emission, light industry) - EN 61000-6-2 (immunity, industry)
- Environment
- ETSI EN 300 019-2 - ETSI EN 300 132-2
- Approvals
- EC tag