Overview>

Products>
 
Electrical Distribution Equipment for Energy Systems
 
Distribution boards for transformation points
Three-phase metering and protection unit in metal/polycarbonate case
Three-phase low voltage selective box
0.4 kV distribution box in metal/polycarbonate case
Connection niche in metal/polycarbonate case
Single-phase metering and protection unit in metal/polycarbonate case
Central point for starting up the public lighting
Level distribution and metering niche in polycarbonate/metal case
Three-phase low voltage junction box
Installation for power factor compensation
 
Low Voltage Electrical Equipment
 
Medium Voltage Electrical Equipment
 
Metallic enclosures
 
Equipment for it and telecom industry
 

Services>

Applications>
   
p1_1_1.gif 

0.4 kV distribution box in metal/polycarbonate case

For network substations on one or two pillars, with 40÷250 (400) kVA power transformers, 20/0,4 kV. It supplies electric power to users from rural areas or suburbs and for street lighting.

Functions

  • it holds and protects from the weather the commutation, protection and metering equipment necessary for the distribution of electric power;
  • it provides the shutting down of the general electric circuit and protects the transformer through the automatic switch that eliminates malfunctions before they reach the transformer, as well as overvoltages of the low-voltage network;
  • it provides disconnection in case of malfunction on each phase of the electrical circuit on the low-voltage outputs in the distribution network through the burning of the fuses, and ensures visible separation for the protection of the personnel through the removal of the safety fuses;
  • it switches on and off the public lighting circuits through a on/off main switch (contactor) for public lighting during night time;
  • it measures the electric power needed by the user in the variants required by the electric power supplier.

 

Technical features:

Rated power 40 ÷ 250 (400) kVA
Thermal and usage rated current   58A ÷ 362 (578) A
Transformer current  50 ÷ 400 (600) /5A, 0.5 class
Rated voltage 400 / 230 V c.a.
Insulation voltage 690 V c.a.
Rated frequency 50 Hz
Normal protection standard  IP 54 (metallic case)
IP 44 (poly carbonate case)

 

Component parts

  • Metallic case which provides the IP 54 protection standard
  • Glass-fiber reinforced polycarbonate case which provides the IP 44 protection standard  
  • Intermediary box (metallic base) that facilitates the easy  connection of all cable types
  • Three-pole or four-pole general automatic breaker
  • Visible separation unit, used in case of interventions in the low-voltage network (delivery at request)
  • Three-phase metering unit of input electric energy  
  • Switch-on point for public lighting with manual or automatic control (with photo cell or time programmer) 
  • Three-phase supplying columns carried out: SIST type safety fuses or vertical three-pole base or vertical three-pole separators
  • Supplying unit for public lighting
  • Single-phase or three-phase electric energy metering unit used for public lighting
  • Indoor single-phase socket for supplying some portable electric tools
  • Indoor lighting circuit for box interventions while the natural light is absent
  • 3 fuses LF – 25/6A on the voltage circuits of meters
  • Terminal housing with connection terminals in null bar variant and main bars for input and output circuits
  • Accessories (pole cable clamps, U-type supporting profile, screws, nuts etc)

Operating conditions:

Erection location Outdoors
Climate group WDr/CT (moderate climate: hot dry / cold temperate)
Environment ambient temperature range during operation -25 ÷ 40°C
Environment ambient temperature range during transportation, storing and erection -40 ÷ 50°C
Average ambient temperature in 24 hours 35°C
Air relative humidity 90% at 25°C
Maximum altitude 2000 m
Pollution degree 3
Over-voltage category Category III
Electro-magnetic mediums Environment A
Life span 25 years


Other information: