varianta carcasa policarbonat 

Three-phase low voltage junction box

It facilitates the junction of the link cables to the public lighting system and provides short-circuit protection for users. It allows the easy detection of network malfunctions as well.

Functions

  • it visibly separates the force circuit (three-phase) in order to protect the operating personnel, through the removal of safety fuses or insulator lugs from the terminal board.

Technical features:

Thermal and usage rated current Max. 100A
Rated power 400/230 V a.c.
Rated insulation voltage 690 V a.c.
Rated frequency 50Hz ÷ 2%
Protection standard IP 54


Component parts

  • Metallic or polycarbonate box which provides the normal IP 54 protection standard
  • Individual supplying columns for lighting units, provided with LF type fuses
  • Junction elements consisting of: three-phase supplying connection/column terminal board provided with SIST type fuses/connectors
  • Pressure gaskets or fittings for input/output supplying cables
  • Fastening accessories on poles

Operating conditions:

Erection location Outdoor
Climate group WDr/CT (moderate climate: hot dry/cold temperate)
Environment ambient temperature range during operation -25 ÷ 40°C
Environment ambient temperature range during transportation, storing and erection -40 ÷ 50°C
Average ambient temperature in 24 hours 35°C
Air relative humidity 90% at 20°C
Maximum altitude 2000 m
Pollution degree 3
Over-voltage category Category III
Electro-magnetic mediums Environment A
Life span 25 years


Other information: