Overview>

Products>
 
Electrical Distribution Equipment for Energy Systems
 
Low Voltage Electrical Equipment
 
Medium Voltage Electrical Equipment
 
Medium voltage electric cells
Primary distribution cells also called "substation cells"
Secondary distribution cells also called "transforming substation cells"
AlfaPower - Prefabricated Substation
 
Metallic enclosures
 
Equipment for it and telecom industry
 

Services>

Applications>
   

Primary distribution cells also called "substation cells"

Technical characteristics:

Rated voltage (Ur) 7.2kV; 12kV; 24kV
Rated current (Ir):
max. 4000 A
Breaking current: max. 50 kA
Short duration admissible rated current (Ik):
Max. 50 kA/1s
Peak admissible rated current (Ip): Max. 125 kA
Rated frequency: 50/60 Hz
Resistance to electric arc action :
Max. 55 kA
Protection degree:
IP 3X

 

General electric characteristics:

Features M.U Value obs
Rated voltage kV 7,2 12 24    
Rated lightning-resistance voltage (phase-ground, phase-phase) kV 60 75 125
Rated 50Hz test resistance voltage kV 20 28 50
Rated current (In):
•    bus-bars
•    switch
•    current transformer
A max.4000
max.4000
max.4000
max. 4000
max. 4000
max. 4000
max. 2500
max. 2500
max. 2500
Breaking current  kA max.50 max. 50 max. 25
Peak admissible rated current kAmax max.125 max. 125 max. 63
Short duration admissible rated current   kAef max.50/1s  max.50/1s  max. 25/1s 
Rated frequency Hz 50 (60*)
Secondary and control circuits voltage V d.c. 24; 48; 60; 110;220. **
a.c. 100; 110; 230.
Usual protection functions ANSI code (***) 27; 37; 46; 50; 51; 59; 67N; 81. **
Normal protection degree
•   in the work position, with all the doors and panels closed
•    between neighboring inner compartments
IP 3X, upon request IP 4X
IP 2X
 
Bar insulation in the main circuits air
Free electric arc resistance inside the cells KA 55 KA 12KV  
25KA   24KV

* upon special request
** according to the beneficiary’s order; other values are also available upon request;
*** the protections according to the ANSI codes are as follows:
 27. protection at minimum voltage;
 37. undercurrent protection;
 46. phase currents imbalance protection;
 50. overcurrent (short-circuit) instantaneous protection;
 51. overcurrent (overload) delayed protection;
 59. maximum voltage protection;
 67N. earthing directional protection;
 81. network frequency variation protection.

Product variants:



Other information: