Primary distribution cells also called "substation cells"
Technical characteristics:
| Rated voltage (Ur) |
7.2kV; 12kV; 24kV
|
Rated current (Ir):
|
max. 4000 A |
| Breaking current: |
max. 50 kA
|
Short duration admissible rated current (Ik):
|
Max. 50 kA/1s |
| Peak admissible rated current (Ip): |
Max. 125 kA |
| Rated frequency: |
50/60 Hz
|
Resistance to electric arc action :
|
Max. 55 kA |
Protection degree:
|
IP 3X |
General electric characteristics:
| Features |
M.U |
Value |
obs |
| Rated voltage |
kV |
7,2 |
12 |
24 |
|
| Rated lightning-resistance voltage (phase-ground, phase-phase) |
kV |
60 |
75 |
125 |
| Rated 50Hz test resistance voltage |
kV |
20 |
28 |
50 |
Rated current (In): • bus-bars • switch • current transformer |
A |
max.4000 max.4000 max.4000 |
max. 4000 max. 4000 max. 4000 |
max. 2500 max. 2500 max. 2500 |
| Breaking current |
kA |
max.50 |
max. 50 |
max. 25 |
| Peak admissible rated current |
kAmax |
max.125 |
max. 125 |
max. 63 |
| Short duration admissible rated current |
kAef |
max.50/1s |
max.50/1s |
max. 25/1s |
| Rated frequency |
Hz |
50 (60*) |
| Secondary and control circuits voltage |
V |
d.c. |
24; 48; 60; 110;220. |
** |
| a.c. |
100; 110; 230. |
| Usual protection functions |
ANSI code (***) |
27; 37; 46; 50; 51; 59; 67N; 81. |
** |
Normal protection degree • in the work position, with all the doors and panels closed • between neighboring inner compartments |
IP 3X, upon request IP 4X IP 2X |
|
| Bar insulation in the main circuits |
air |
| Free electric arc resistance inside the cells |
KA |
55 KA |
12KV |
|
| 25KA |
|
24KV |
* upon special request ** according to the beneficiary’s order; other values are also available upon request; *** the protections according to the ANSI codes are as follows: 27. protection at minimum voltage; 37. undercurrent protection; 46. phase currents imbalance protection; 50. overcurrent (short-circuit) instantaneous protection; 51. overcurrent (overload) delayed protection; 59. maximum voltage protection; 67N. earthing directional protection; 81. network frequency variation protection.
Product variants:
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system, of 12kV / max. 1250A / max. 31.5kA provided with Siemens equipment >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 12kV / max. 1250A / max. 31.5kA, provided with Schneider equipment >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 12kV / max. 2500A / max. 31.5kA, provided with ABB equipment with vacuum commutation >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 12kV / max. 2500A / max. 31.5kA, provided with ABB equipment with SF6 commutation >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 24kV / max. 1250A / max. 25kA, 800 mm width, provided with ABB equipment >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 24kV / max. 1250A / max. 25kA, 800 mm width, provided with Siemens equipment >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 24kV / max. 1250A / max. 31.5kA, provided with ABB equipment >
-
Medium voltage electric cells, in metallic case, for indoor use, with simple bar system of 24kV / max. 1250A / max. 25kA, with 1000mm width provided with Siemens (3AH) equipment >
Other information:
|